Heat not keeping up during cold snap
Tenant at time of issue: Theo Martin
Sample PDF export
Read-only sample data. Anyone with the share link can view the record until it expires.
Sample share link expires August 20, 2026.
Record completeness
Strong record: tenant report, vendor finding, photos, and completion note attached.
Weak-record warning example: no completion photo attached.
Timeline
Apartment was 58 degrees at 6 AM. Heat is on but air from vents is barely warm. Tenant has a child home from school today.
Dropped off two oil-filled space heaters and confirmed tenant has clear outlets. Advised tenant not to use extension cords.
Northside HVAC scheduled emergency diagnostic for same day. Technician asked for filter size and furnace closet access.
Technician found inducer motor failing intermittently. Furnace restarted, but motor is noisy and may stop again. Part ordered.
Tenant reported unit is holding 67 degrees with temporary heaters overnight. Follow-up repair remains scheduled when part arrives.
Status changed from open to in progress while waiting for inducer motor replacement.